Brand new Rheem R92P series 70,000 btu downflow. Factory installed over temp limit (120 degrees) 1/16″ from the heat exchanger. Shimmed out to 1/2″ until factory can send a repair. Clearly a design flaw. Take note if you install a 90+ Rheem.